GVSUPS40KR0B5GS Technical Specifications
Galaxy VS UPS 40kW 480V with N+1 module
Output
Max Configurable Power (Watts)
40.0kWatts / 40.0kVA
Output Voltage Distortion
Less than 3%
Output Frequency (sync to mains)
50Hz, 60Hz
Output Frequency (not synced)
50Hz +/-0.1% for 50Hz nominal, 60Hz +/-0.1% for 60Hz nominal
Load Crest Factor
2.5
Topology
Double Conversion Online
Waveform type
Sinewave
Overload Operation
150% for 1 minute 125% for 10 minutes
Output Voltage THD
<1% linear load and <3% non-linear load
Output Voltage Tolerance
+/-1% after 50ms
Bypass
Built in static bypass
Input
Input frequency
40-70Hz
Input voltage range for main operations
408 – 552 (480)V
Input Total Harmonic Distortion
Less than 6% at full load
Maximum Short Circuit Withstand (Icw)
65.0kAmps
Input Power Factor at Full Load
0.99
Batteries & Runtime
Battery type
VRLA
Nominal Battery Voltage
480VDC
End of Discharge Maximum Battery Current
109.0A
End of Discharge Battery Voltage
384VDC
Efficiency
View Efficiency Graph
Communications & Management
Control panel
Touchscreen LCD user interface
Audible Alarm
Audible and visible alarms prioritized by severity
Physical
Maximum Height
78.0inches (1970MM, 197.0CM)
Maximum Width
22.0inches (550MM, 55.0CM)
Maximum Depth
34.0inches (847MM, 84.7CM)
Net Weight
551.16lbs. (250.0KG)
Shipping weight
552.0lbs. (250.0KG)
Shipping Height
82.0inches (2082MM, 208.2CM)
Shipping Width
30.0inches (755MM, 75.5CM)
Shipping Depth
40.0inches (1010MM, 101.0CM)
Color
Gloss level 85%, RAL 9003, White
Environmental
Operating Temperature
32 – 104 °F (0 – 40 °C)
Operating Relative Humidity
0 to 95% non-condensing %
Operating Elevation
0-3300ftft (0-990meters)
Storage Temperature
-15 – 40 °C
Storage Relative Humidity
10 to 80% non-condensing %
Storage Elevation
0-10|000ftft (0-3meters)
Audible noise at 1 meter from surface of unit
54.0dBA
Online thermal dissipation
4728.0BTU/hr
Reviews
There are no reviews yet.