GVSUPS20KB4GS Technical Specifications
Galaxy VS UPS 20kW 480V, 1 internal 9Ah modular
Output
Max Configurable Power (Watts)
20.0kWatts / 20.0kVA
Output Frequency (sync to mains)
50 Hz, 60 Hz
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
Load Crest Factor
2.5
Topology
Double Conversion Online
Waveform type
Sine wave
Overload Operation
150% for 1 minute 125% for 10 minutes
Output Voltage Tolerance
+/-1% after 50ms
Bypass
Built-in Static Bypass
Input
Input frequency
40 – 70 Hz
Input voltage range for main operations
408 – 552 (480)V
Input Total Harmonic Distortion
Less than 3% for full load
Maximum Short Circuit Withstand (Icw)
65.0kAmps
Input Power Factor at Full Load
0.99
Batteries & Runtime
Battery type
VRLA
Nominal Battery Voltage
480V
End of Discharge Maximum Battery Current
54.0A
End of Discharge Battery Voltage
384 Vdc
Efficiency
View Efficiency Graph
Communications & Management
Interface Port(s)
GVS_350mm_AirFilter, GVS_350mm_Seismic, GVSAIO_BypassCabinetCables_UL, GVSAIO_MBP_UL
Control panel
Touch Screen LCD User Interface
Audible Alarm
Audible and visible alarms prioritized by severity
Available SmartSlot™ Interface Quantity
1
Physical
Maximum Height
58.46inches (1485MM, 148.5CM)
Maximum Width
20.51inches (521MM, 52.1CM)
Maximum Depth
33.35inches (847MM, 84.7CM)
Net Weight
1014.13lbs. (460.0KG)
Shipping weight
1080.27lbs. (490.0KG)
Shipping Height
66.14inches (1680MM, 168.0CM)
Shipping Width
25.2inches (640MM, 64.0CM)
Shipping Depth
38.98inches (990MM, 99.0CM)
Color
Gloss level 85%, RAL 9003, White
Environmental
Operating Temperature
32 – 104 °F (0 – 40 °C)
Operating Relative Humidity
0 – 95 (non-condensing) %
Operating Elevation
0-3281ft (0-984.3meters)
Storage Temperature
-15 – 40 °C
Reviews