GVX500K750HS Technical Specifications
Galaxy VX 500kVA Scalable to 750kVA 400V
Output
Max Configurable Power (Watts)
750.0kWatts / 750.0kVA
Output Frequency (sync to mains)
50 Hz, 60 Hz
Output Frequency (not synced)
50Hz +/- 0.1% for 50Hz nominal
Other Output Voltages
380, 415, 440
Load Crest Factor
3 with THC <5%
Topology
Double Conversion Online
Waveform type
Sine wave
Overload Operation
150% for 1 minute 125% for 10 minutes
Output Voltage THD
< 2% linear load and <3% non-linear load
Input
Input frequency
40 – 70 Hz
Input Total Harmonic Distortion
Less than 3% for full load
Other Input Voltages
380, 415, 440
Maximum Short Circuit Withstand (Icw)
100.0kAmps
Batteries & Runtime
Battery type
No internal battery – uses external battery system
Nominal Battery Voltage
480V
End of Discharge Battery Voltage
384 Vdc
Efficiency
View Efficiency Graph
Communications & Management
Control panel
7″ Touch Screen Display
Audible Alarm
Audible and visible alarms prioritized by severity
Available SmartSlot™ Interface Quantity
2
Physical
Maximum Height
77.56inches (1970MM, 197.0CM)
Maximum Width
106.3inches (2700MM, 270.0CM)
Maximum Depth
35.43inches (900MM, 90.0CM)
Net Weight
4144.69lbs. (1880.0KG)
Shipping weight
5714.39lbs. (2592.0KG)
Shipping Height
84.65inches (2150MM, 215.0CM)
Shipping Width
124.8inches (3170MM, 317.0CM)
Shipping Depth
41.73inches (1060MM, 106.0CM)
Color
White
Environmental
Operating Temperature
32 – 104 °F (0 – 40 °C)
Operating Relative Humidity
0 – 95 (non-condensing) %
Operating Elevation
0-3333ft (0-999.9meters)
Storage Temperature
-15 – 40 °C
Storage Relative Humidity
0 – 95 (non-condensing) %
Storage Elevation
0-50000ft (0-15000meters)
Audible noise at 1 meter from surface of unit
69.5dBA
Online thermal dissipation
82435.0BTU/hr
Protection Class
IP 20
Conformance
Approvals
cUL Listed, C-tick, CE, IBC 2012, IEC 62040-1-1, IEC 62040-2, IEC 62040-3, IEC 62040-4, ISTA 2B, UL 1778 5th edition
Reviews
There are no reviews yet.